Residential Electrical Load Calculator (NEC 2023)
Put in the house size, appliances and heating or cooling. You'll see the calculated service load for a single-family home using the NEC 220.82 optional method and the standard method, with each line tied to its NEC section.
How to use itCalculator (NEC 2023)
For one single-family home on a 120/240 V service. The optional method is only allowed when the service or feeder is rated 100 A or more (NEC 220.82(A)). Amps are VA ÷ 240. Neutral load (220.61) is not calculated.
Uses NEC 2023; the 2026 NEC (Article 120) gives lower results; check which edition your AHJ uses.
How to use it
- Floor area: the living area from the outside dimensions. Leave out open porches and unfinished spaces that can't become living space. Under the 2023 NEC, garages are no longer left out of the 3 VA/ft² figure for the standard method (220.41), so check which code edition your area uses.
- Circuits: a home needs at least two 20 A small-appliance circuits and one laundry circuit (210.11(C)). Add any extras you have.
- Appliances: use the nameplate rating. For a separate cooktop and up to two wall ovens in the same room, add their kW together and put the total in the range box (Table 220.55, Note 4).
- Heating and cooling: pick the type of electric heat. For a heat pump with backup strips, tick the box if the controls stop the strips and compressor running together.
- Read the results: both methods are shown. The optional method usually gives a smaller number for a whole-house service. Open "Show the math" to see every line and its NEC section.
How each method works (2023 NEC)
Optional method, 220.82: add 3 VA per square foot, 1,500 VA for each small-appliance and laundry circuit, and the nameplate rating of the range, ovens, dryer, water heater and other fastened-in-place appliances (220.82(B)). Take the first 10,000 VA at 100% and the rest at 40%. Then add the largest one heating or cooling load from 220.82(C):
- A/C at 100%, or a heat pump with no backup heat at 100%.
- A heat pump compressor at 100% plus backup heat at 65%. If the controls lock out the compressor while the strips run, leave the compressor out.
- Space heat at 65% if there are fewer than four separately controlled units, or 40% if there are four or more.
- Thermal storage heat at 100%.
Standard method, Part III: general lighting at 3 VA/ft² (220.41) plus 1,500 VA per small-appliance and laundry circuit (220.52), reduced by Table 220.45 (first 3,000 VA at 100%, the next 117,000 VA at 35%, the rest at 25%). Then fastened-in-place appliances, at 75% when there are four or more (220.53). The dryer is 5,000 VA or its nameplate, whichever is larger (220.54). The range comes from Table 220.55: 8 kW for one range up to 12 kW, plus 5% for each kW over 12. An EV charger is 7,200 VA or its nameplate, whichever is larger (220.57). Heating and A/C: only the larger one counts (220.60). Finally, 25% of the largest motor is added (220.50 and 430.24).
Older code editions: in the 2020 NEC, 220.41 was 220.12 and Table 220.45 was Table 220.42. The math is the same apart from the garage rule. The worked examples in NEC Informative Annex D (D1(a), D2(a) and D2(b)) give the same answers as this calculator.
Questions
Which method should I use?
For a whole single-family home on a service of 100 A or more, the optional method is allowed and usually gives a lower load. The standard method works for any dwelling. Your inspector can tell you which one they want to see.
Can I use this to add an EV charger or heat pump to an existing house?
Additions to an existing home have their own rules in NEC 220.83, and some areas allow load monitoring (220.87). This calculator does a full new calculation, so have an electrician check an add-on.
Does this size the wire?
No. It gives the calculated load. Wire size depends on 310.12, terminal ratings and local amendments.
Is anything I type saved or sent?
No. The math runs in your browser and nothing is uploaded.
Planning backup power? The generator size calculator estimates running and starting watts for the appliances you want to run.
Estimate only. This calculator follows the 2023 NEC as written and is not engineering advice. Local amendments and the code edition your area uses can change the result. Verify with your AHJ (local inspector) and a licensed electrician before you buy or install equipment.